This is an archived version. The product may no longer correspond to the latest state of the art; Gira expressly recommends using the current software/firmware.
Operating system: Windows 7, Windows 8, Windows 10
Free hard drive space: at least 16 GB
RAM: at least 4 GB
"Maintenance functions" refers to firmware updates, restarts and factory resets which are carried out through the Action Center (GPA menu -> Action Center).
In some cases, logic may not have been executed. This error occurred if the device (Gira X1 or Gira L1) on which the logic was to be executed was deleted from the project and located again.
Display of the error message "Project integration check failed" on start-up and on export of projects. This error message occurred in two situations and has been rectified in both cases:
Before a device action is carried out, it is recommended that you unlock the device separately. This can be done in the "Building and devices" view (right-click on the device -> lock/unlock device).
When you have updated the firmware of a Gira L1 for which no password had been previously assigned or which has no device password sticker, the new password following a firmware update is "device".
Please change the device password during configuration.
If a project is copied or read out of a device, or the project copy is loaded from the device, the physical device has to be connected to the device template again.
Click on the located device and then click on "Undo device assignment" in the properties bar. The device will be shown under "New devices found" again and can then be pulled back over to the device template.
The OpenVPN function in the Gira X1 only works in conjunction with DHCP. There must be a DHCP server in the network and the Gira X1 network must be initialised via DHCP and not by means of static IP configuration. This is necessary in order for the OpenVPN server to be able to assign an IP address to connecting clients. Should you wish to always use the Gira X1 with a fixed IP address, you can generally configure the DHCP server (usually part of the Internet router) in such a way that it always assigns the same IP address to the Gira X1.
Retentive data is saved by the Gira L1 every 15 minutes. Data may be lost within this time period in the event of power failure.
The Gira X1/L1 offers several physical addresses. When the physical address is programmed within the ETS, only the device address is adopted. The additional addresses are only adopted after downloading the application program.
After project download, the Gira X1/L1 responds to the first event with a delay of approx. 1 second.
A solution description is specified in the "Troubleshooting" directory. This is found in the installation directory of the Gira Project Assistant.
Example: "C:\Program Files (x86)\Gira\Gira Project Assistant\2.1\Troubleshooting"